Home | Company Info | Products | Articles | Contact Us | Search Our Site | Site Map
OmniSmart Series

OmniPro (3398 bytes)

OmniPro UPS Systems

Line interactive power protection for PCs and servers

OmniPro UPS Systems combine automatic voltage correction with long-lasting battery backup power. These microprocessor controlled systems keep you working through voltage problems without using battery power, and reliable battery backup keeps you working through power outages.

  • Multi-level automatic voltage regulation keeps equipment working through low voltage (brownouts) and high voltage conditions without using battery power
  • Reliable battery power keeps your equipment running safely through blackouts
  • RFI/EMI line noise filtering prevents interference (i.e. from motors, lights and radio transmissions) from affecting your computer
  • NEW! Select models feature:
    • 6 outlets (3 UPS and surge protected, 3 surge-only protected) to safeguard your computer and all peripherals
    • Built-in RJ11 jacks for modem/fax surge protection; 675 VA models protect two modem/fax lines simultaneously
    • Serial port for use with optional PowerAlert Software
    • Convenient battery replacement doors
 

 

Model OmniPro 280 OmniPro 450 OmniPro 675
Input/Output Voltage 120 120 120
Input/Output Hz 60 60 60
Output VA 280 450 675
Output Watts 175 300 425
UPS Type Line Interactive Line Interactive Line Interactive
Online Waveform Pure Sine Pure Sine Pure Sine
On Battery Waveform PWM Sinusoidal PWM Sinusoidal PWM Sinusoidal
Voltage Regulation Line interactive system corrects voltage to nominal levels, boosting input between 92 to 105 volts and reducing input between 134 and 150 volts. Output voltage in battery mode is regulated to 120 volts +/- 5%. Line interactive system corrects voltage to nominal levels, boosting input between 92 to 105 volts and reducing input between 134 and 150 volts. Output voltage in battery mode is regulated to 120 volts +/- 5%. Line interactive system corrects voltage to nominal levels, boosting input between 92 to 105 volts and reducing input between 134 and 150 volts. Output voltage in battery mode is regulated to 120 volts +/- 5%.
Full Load Runtime (min.) 5 5 5
1/2 Load Runtime (min.) 17 17 17
Typical Runtime (min.) up to 28 min. up to 38 min. up to 52 min.
Recharge Rate (hours) 2-4 2-4 2-4
Transfer time (ms.) 2-4 2-4 2-4
Joules 360 360 360
Maximum Surge Current (amps) 27,000 27,000 27,000
Suppression Response Time Less than one nanosecond Less than one nanosecond Less than one nanosecond
EMI/RFI Noise Reduction Greater than 40 dB @ 1 MHz Greater than 40 dB @ 1 MHz Greater than 40 dB @ 1 MHz
High Volt Switch to Battery 150 150 150
Low Volt Switch to Battery 92 92 92
Outlet Type (f) 3 NEMA 5-15R 6 NEMA 5-15R (3 UPS/ 3 Surge) 6 NEMA 5-15R (3 UPS/3Surge)
Cord Length 6 ft. 6 ft. 6 ft.
Plug Type (m) NEMA 5-15P NEMA 5-15P NEMA 5-15P
Dimensions HxWxD (inches) 8.25 x 4.25 x 5.75 8.25 x 4.75 x 7 10.5 x 4.75 x 7
Shipping Weight (lb.) 13 15.5 20.5
Fax/Modem Surge Protection Not included. Order add-on module #DTEL2 Set of RJ11 jacks protects a single phone line. Set of RJ11 jacks protects two phone lines.
Network Interface Port None None DB9 port for use with optional PowerAlert software
Software and Cable Included N/A N/A Not included. Order optional p/n 75-1095
Product Warranty (yr.) 2 2 2
Ultimate Lifetime Insurance $50,000 $50,000 $50,000
Battery Access Technician Battery Access Door Technician
Controls, Indicators, and Additional Features On/off switches, LEDs indicate on-line, on-battery status. On/off and Self test/alarm silence switches, LEDs indicate on-line, on-battery, voltage correction, and battery low/replace, audible alarms. 3 UPS supported and 3 Surge protected outlets. On/off and Self test/alarm silence switches, LEDs indicate on-line, on-battery, voltage correction, and battery low/replace. Audible alarms.