STANDARD CLASS

BUILDING ENTRY PROTECTOR
Ipeak = 160kA




READY TO GO!
Easy Installation - less than 30 minutes
- Mount pre-tested SF160M to wall
- Connect Micro-Z Cable to panel
- Apply power - system is protected

20-Year Warranty

Free modules for life

Free fuses for life

ulbal1i1.gif (1059 bytes)

UL 1449
3rd Edition Listed

ANSI/IEEE C62.41-1991
Category C

SF160M (9400 bytes)

DESCRIPTION FEATURES
The SF160M offers superb protection at the main service panel for most applications. Computers, sensitive business equipment, and other high tech equipment are guarded from damage, errors, and downtime resulting from high speed transients.

The SF160M system provides a better transient pathway to ground. It consists of a low impedance cable having only 1/3 the voltage drop of conventional cabling and a protector design with a very low internal voltage drop. This results in a lower transient exposure to sensitive downstream equipment. The plug-in, pluck-out protection modules guarantee a quick and easy  5 minute repair in the unlikely event of catastrophic transients.

The on-board diagnostics include front panel and internal LEDs, transient event counter, audible alarm, and remote alarm. In addition, the unit is housed in a rugged indoor/outdoor NEMA4 enclosure.

SF160M Data Sheets (377KB)
SF160M Engineering Specifications (24KB)
SF120M & 160M Y & T Installation Instructions (146KB)
SF120M & 160M Delta Installation Instructions (108KB)

  • Ipeak of 160,000 Amps per phase - major surge current diversion
  • Built-in redundancy - dual-level protection for dependable performance.
  • All modes protected, L-N, L-G, L-L, N-G.
  • Patented "low impedance" MICRO-Z design.
  • Large cross-sectional copper conductors.
  • MICRO-Z cable provided at no cost.
  • Continuous on-line status monitoring.
  • Diagnostics - pinpoints the problem location.
  • Remote status monitoring capability.
  • Personnel safety - integrated power disconnect with LEXAN dead-front construction. Only MCG has it!
  • Warranty - 20 year on Protector and a lifetime replacement of modules and fuses without charge.

CONFIGURATIONS:

MODEL RATED VOLTAGE DESCRIPTION

ENERGY ABSORPTION
(8/20s)
JOULES TOTAL

UL 1449 SURGE VOLTAGE (8/20us)
500a

SF160M-120T 120/240VAC 1, 3W+GND 8,772 400
SF160M-120Y 120/208VAC 3, 4W+GND, WYE 8,772 400
SF160M-220Y 220/380VAC 3, 4W+GND, WYE 23,520 700
SF160M-240Y 240/415VAC 3, 4W+GND, WYE 23,520 700
SF160M-240D 240VAC 3, 3W+GND, DELTA 20,160 700
SF160M-240DCT 240/120/120VAC 3, 4W+GND, HI-LEG 15,064 700/400
SF160M-277Y 277/480VAC 3, 4W+GND, WYE 25,200 800
SF160M-480D 480VAC 3, 3W+GND, DELTA 36,000 1500

ELECTRICAL SPECIFICATIONS

MAX. CONTINUOUS OPERATING VAC:  115%
RESPONSE TIME:  <5 NANOSECONDS
MODES OF PROTECTION:  L-N, L-G, L-L, N-G
SURGE CURRENT/PHASE (8/20s) - 1 EVENT:  160kA
SURGE LIFE/PHASE (8/20s) - 10,000 IMPULSES:  6kA
FILTER ATTENUATION MIL STD 220A (50ohm):  120VAC 240VAC 277VAC 480VAC
-30db:  100kHz 25kHz 80kHz 80kHz
-40db:  200kHz 100kHz 180kHz 180kHz
-50db:  280kHz 180kHz 210kHz 250kHz
-55db:  310kHz 200kHz 390kHz 390kHz
PROTECTION PRESENT INDICATORS:  GREEN LED
REDUCED PROTECTION INDICATOR:  RED LED
ADDITIONAL STATUS INDICATORS:  AUDIBLE ALARM, EVENT COUNTER, REMOTE DRY CONTACTS
OPERATING ALTITUDE:  13,000 ft. (4000m)
TEMPERATURE (OPERATING/STORAGE):  -40 to +70C/-40 to +85C
ENCLOSURE:  NEMA 4, 14 GAUGE STEEL
DIMENSIONS:  12" x 10" x 5"
MOUNTING:  12.75" x 8"/.3125 ID - 4 HOLES
CABLE CONNECTION:  MICRO-Z CABLE SUPPLIED FREE
SHIPPING WEIGHT:  23 lbs.