Home | Company Info | Products | Articles | Contact Us | Search Our Site | Site Map
Displays | Temp. Sensors | Humidity Transmitters | Pressures Transmitters | Current Sensors
Interface Devices | Accessories

High Temperature Transmitters
ACI/TT100-HT
ACI/TT1000-HT



Product Description:

The ACI/TT100-HT and ACI/TT1000-HT Series temperature transmitters incorporate a Class B thin film platinum RTD sensor which conforms to DIN-IEC-751 platinum RTD standards.

ACI produces two temperature transmitters, the ACI/TT100-HT for use with a 100 ohm RTD input and the ACI/TT1000-HT for use with a 1000 ohm RTD input. The transmitters produce a linear 4-20 mA output carried on a two wire system. Optional voltage ranges of 1 to 5 or 2 to 10 VDC can also be ordered. The input voltage to the transmitter may vary from 7-35 VDC. The transmitter is supplied factory calibrated and is protected from EMI and RF interference when using a 4-20 mA output. The transmitters output current can be limited upon request.

One of the most important features of the ACI/TT100-HT and ACI/TT1000-HT temperature transmitters is that they are air encapsulated. This allows the sensor to have a more stable output since the sensing element isn't subjected to the constant expansion and contraction of the encapsulation materials. The sensors are mounted in a 1/4" diameter stainless steel probe and come with standard 24" Nickel Plated Fiberglas leads except for the remote probes which come with 10' leads.

Some of the typical applications are for Stacks, Boilers, Oil Baths, Process Controls, Commercial Ovens, Plastics Processing, Bearings, Incubators, and Truck or Vehicle Engines.

These units are offered in Duct, Duct without box, Immersion, and Remote Probe configurations.

Product Specifications:
Input 2 wire Platinum 100/1000 Ohm RTD Transmitter Accuracy +/- 0.1% of Span
Output 2 wire, Linear 4 to 20mA DC current Sensor Accuracy0.12% @ 32F
Supply Voltage 7 to 35 VDC No Polarity Sensitivity Temperature Sensor Range -40 to 842F
Linearity +/- 0.05% of span Transmitter Operating Range 32 to 158F

DuctOutside
ImmersionRemote Probe


Ordering Information:
Span ConfigurationOutput
ACI/ -[]-[] -[]-[]
TT100-HT Specify(D) Duct - 4", 8", 12" (1) 1 to 5VDC
TT1000-HT (DO) Duct w/out box 4", 8", 12" (2) 2 to 10VDC
(I) Immersion 4", 8" (4) 4 to 20mA
(RP) Remote Probe

Back To Top
2004 Sentinel Power Inc. All rights reserved.
Last Updated 03/18/10