Home | Company Info | Products | Articles | Contact Us | Search Our Site | Site Map
Displays | Temp. Sensors | Humidity Transmitters | Pressures Transmitters | Current Sensors
Interface Devices | Accessories

Current Operated Solid-State Relays
ACI/MM-1
ACI/MM-2



Product Description:

The ACI/MM-1 and ACI/MM-2 is a solid -state current operated relay with two user-adjustable level settings for independently monitoring starting and running currents. Each 4-turn adjustment sets the threshold of a precision comparator which trips whenever the starting or running current exceeds the setting. Two settable timers, each triggered by its own comparator, provides a 0.2 to 10 second delay in which the normal relay operation is inhibited. These delays cover the normal start time and whatever running-overload time the user needs to avoid the nuisance trips. The contact can be wired directly to the starters. The MM-1 series is used to monitor overloads and the MM-2 series is used to monitor underloads.

The switch can sense current from 1 to 200 Amps continuous, up to 1000 VAC and has 3 jumper selectable input ranges. The sensors trip point is adjustable from 1 to 200A using the four turn potentiometer. The output is a normally open or normally closed solid state relay which may be used to switch either AC or DC power. A Red LED displays the On/Off status of the switch and is standard on all sensors unless specified. Power for the MM series current sensors is induced from the conductor being monitored. All ACI/MM-1 and ACI/MM-2 series current sensors come with a 5 year unconditional warranty

The sensor is a simple, cost effective solution for monitoring motors as well as General overload vs. Time protection.
· Direct connection to PC's and other control systems
· Direct control light loads such as contactors, lamps and relays
· Monitors motors and equipment which are subject to jamming and unusual starting or running conditions

Product Specifications:
Amperage Range 1 to 200 Amps Trip Set-Point 4 Turn Adjustable Potentiometer
Input Ranges 1-12A, 12-50A, and 50-200A Operating Range -15 to 60°C
(5 to 140°F)
Output Solid State Relay Sensor Hole Size 0.75" diameter
Isolation 1000 VAC MountingIntegral mounting bracket
Switching
Characteristics
AC: Up to 1A cont. at up to 240VAC, 50-60HZ
DC: Up to 0.15A cont., at up to 30VDC
Off State Leakage AC: with RC snubber and status LED(standard) 3.5 mA @ 120VAC; 2mA w/out
DC: N/O 1.1mA max. @ 24 VDC; No Leakage
N/C: 1.4mA max. @ 24VDC; 10uA/DCV





Ordering Information:
ACI/ [ ][ ] [ ]
MM1AC-NO (1) 1 TO 12 Running Amps ( )-Standard
MM1AC-NC (2) 12 to 50 Running Amps (NL)-Minimal Off-State Leakage
MM1DC-NO (3) 50 to 200 Running Amps
MM1DC-NC

Example: ACI/MM1AC-NO-1 or ACI/MM1AC-NO-1-NL

Back To Top
© 2004 Sentinel Power Inc. All rights reserved.
Last Updated 03/18/10