Product Description:

ACI's analog current sensors monitor the current flowing to electrical equipment. The magnitude of the current is directly converted to a linear output signal useable by a controller. The signal is used by a controller to detect conditions such as over/underload, excessive wear, broken belts, and mechanical failure in motors and pumps. The ACI/C100 and ACI/C200's are the solid-core version, where the conductor runs through the sensor, no cutting, taping, or rerouting is required. The ACI/SC100 and ACI/SC200's are the split-core versions of the C100 and C200's making them ideal for retrofit applications. The current sensors are accurate, reliable, easy to install, and requires less service than differential pressure switches, flow switches, and paddle wheels.

The ACI/C100 has an accuracy of, 1% of full scale, in the frequency range from 50 to 60Hz with currents up to 200A. The sensor outputs a 2-wire 0-5 VDC signal. The zero and span is factory calibrated and is jumper selectable from 1 to 50 or 10 to 200A. The sensors power is induced from the current being monitored.

The ACI/C200 is an extremely accurate sensor, 0.5% of full scale, in the frequency range from 20 to 100Hz with currents up to 200A. The sensor outputs a 2-wire 4-20mA or 1-5VDC signal. The zero and span is factory calibrated and is jumper selectable from 0 to 50 or 0 to 200A. The sensor is loop powered and requires an input voltage of 10 to 40 VDC. All ACI/C100 and ACI/C200 Series current sensors come with an unconditional 5 Year Warranty.

Product Specifications:
Model # Amperage Rating Sensor Output Accuracy Supply Voltage Isolation
ACI/C100-1 1-10, 2-20, 5-50 Amps 0 to 5 VDC 1% @ 50-60HZ
2% @ 20-100HZ
Induced1000 VAC
ACI/C100-2 10-100, 15-150, 20-200 Amps 0 to 5 VDC 1% @ 50-60HZ Induced1000 VAC
ACI/C200-1 0-10, 0-20, 0-50 Amps 4 to 20 mA +/- 0.5% FS 10-40VDC Loop Powered 1000 VAC
ACI/C200-2 0-100, 0-150, 0-200 Amps 4 to 20 mA +/- 0.5% FS 10-40VDC Loop Powered 1000 VAC
ACI/SC100-1 1-10, 2-20, 5-50 Amps 0 to 5 VDC 1% @ 50-60HZ
2% @ 20-100HZ
Induced1000 VAC
ACI/SC100-2 10-100, 15-150, 20-200 Amps 0 to 5 VDC 1% @ 50-60HZ Induced1000 VAC
ACI/SC200-1 0-10, 0-20, 0-50 Amps 4 to 20 mA +/- 0.5% FS 10-40VDC Loop Powered 1000 VAC
ACI/SC200-2 0-100, 0-150, 0-200 Amps 4 to 20 mA +/- 0.5% FS 10-40VDC Loop Powered 1000 VAC





Ordering Information:

ACI/[ ]
Current Ranges Analog Output Core Type
ACI/C100-1 1-10, 2-20, 5-50 Amps 0 to 5 VDCSolid Core
ACI/C100-2 10-100, 15-150, 20-200 Amps 0 to 5 VDCSolid Core
ACI/C200-1 0-10, 0-20, 0-50 Amps 4 to 20 mASolid Core
ACI/C200-2 0-100, 0-150, 0-200 Amps 4 to 20 mASolid Core
ACI/SC100-1 1-10, 2-20, 5-50 Amps 0 to 5 VDCSplit Core
ACI/SC100-2 10-100, 15-150, 20-200 Amps 0 to 5 VDCSplit Core
ACI/SC200-1 0-10, 0-20, 0-50 Amps 4 to 20 mASplit Core
ACI/SC200-2 0-100, 0-150, 0-200 Amps 4 to 20 mASplit Core

Example: ACI/SC100-1