Home | Company Info | Products | Articles | Contact Us | Search Our Site | Site Map
Displays | Temp. Sensors | Humidity Transmitters | Pressures Transmitters | Current Sensors
Interface Devices | Accessories

Analog Isolation Module

 

ACI/AIM1

Product Description:

The ACI/AIM1 optically isolates the analog input from the output produced. The output is a proportional, 1:1 ratio, to the input. Inputs of 0 to 5 volts, 0 to 10 volts, and 0 to 20 mA are accepted. A 24VAC external supply is required, an on-board 24VAC transformer supplies the isolated output. LEDs indicate power status for both supplies.

Isolation modules are used to separate instruments using separate ground planes, eliminating problems such as ground loops. The AIM1 isolates analog inputs up to 600VAC or 1500VDC. Selection of voltage or current input (sink or source) and voltage or current output is done on the board with jumpers.

The ACI/AIM2 is also available upon request. The AIM2 is a rescaleable isolation module. Both the input and the output may be rescaled on the AIM2. Please contact us for further information on the ACI/AIM2.
 

 



Product Specifications:

Voltage Isolation Current Isolation
Supply Voltage 24 VAC +/- 10%Supply Voltage 24 VAC +/- 10%
Operating Range -20 to 150FOperating Range -20 to 150F
Input Signal 0 to 5VDC
0 to 10VDC
Input Signal 0 to 20 mA
Input Impedance 20,000 OhmsInput Impedance 250 Ohms
Output Signal Voltage = 0 to 5VDC
0 to 10VDC
Output Signal 0 to 20 mA source
0 to 20 mA sink
Output Impedance 5000 Ohms minOutput Impedance 500 Ohms max
Accuracy +/- 1%Accuracy Source: +/- 2% Sink: +/- 1%
Linearity +/- 1%Linearity +/- 1%

PDF Specifications
PDF Installation Instructions



Ordering Information:
ACI/AIM1 ACI/AIM2

Example: ACI/AIM1 OR ACI/AIM2